| Sign In | Join Free | My burrillandco.com |
|
| Ask Lasest Price | |
| Brand Name : | Xingjin |
| Model Number : | QMH15/80, QMH15/90 |
| Certification : | CAL,CMA,CNAS,ILAC-MRA,CCC |
| Price : | negotiation |
| Payment Terms : | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
| Supply Ability : | 300 sets per month |
| Delivery Time : | 10-15 working days |
The 90L 15MPa Red Pipe Network Type IG100 Nitrogen Fire Suppression System is an inert gas fire suppression solution that uses nitrogen to extinguish fires safely in occupied spaces. It is engineered for reliable performance in environments where water-based or chemical suppression could cause damage to sensitive equipment and materials.
The IG100 nitrogen fire suppression system is a form of fire suppression that employs nitrogen gas to extinguish fires. As an inert gas that prevents combustion, nitrogen is suitable for use in populated spaces. Normal operation proceeds as follows:
The IG100 system is commonly used in areas where water-based fire suppression systems may cause significant damage, including electrical equipment rooms, data centers, archives, museums, and other facilities housing valuable equipment or sensitive materials.
The IG100 system should be designed, installed, and maintained by qualified professionals in accordance with applicable regulations and standards. System design should account for room volume, fire load, and ventilation to ensure proper fire suppression effectiveness. Regular inspections and maintenance are necessary to keep the system in optimal working condition and to address any potential issues.
| No. | Specification | Technical Parameter |
|---|---|---|
| 1 | Working Pressure | 15 MPa |
| 2 | Device Model | QMD15/80 | QMD15/90 |
| 3 | Capacity | 80 Ltr | 90 Ltr |
| 4 | Filling Capacity of Gas | 14.25 kg | 16.04 kg |
| 5 | Outside Diameter of Cylinder | Φ279 mm | Φ325 mm |
| 6 | Height of Cylinder | 1578+73 mm | 1345+60 mm |
| 7 | Spraying Time | ≤10 s |
| 8 | Max Filling Rate | 0.178 kg/L |
| 9 | Power | DC24V / 1.6A |
| 10 | Nitrogen Pressure of Driving Device | 6.0 ± 1.0 MPa (20℃) |
| 11 | Condition of Reserving Room for Container | Temperature: 0 ~ 50℃ |
| 12 | Max Working Pressure | 17.2 MPa |
| 13 | Min Working Pressure | 13.6 MPa |
Fire suppression systems are designed to detect, contain, and extinguish fires in buildings, vehicles, and other enclosed spaces. Common applications include:
Fire suppression systems are crucial for preventing the disastrous impacts of fires on people and property. To ensure they work in an emergency, they should be installed and maintained by trained experts. For the highest level of safety, fire suppression systems should be used in conjunction with fire prevention strategies such as routine fire drills, smoke detectors, and fire extinguishers.

Each unit is first packed with polyfoam and then placed into a wooden case. When required to meet client preferences or safety requirements, goods may also be arranged on a pallet.





|